User Manual
2 / 6
Siemens Desigo S7 TP700 Touch Panel local HMI CM1N9290en_03
Building Technologies 2018-03-01
Application
Local operation and monitoring distinguishes itself through the following system
and product features:
• Plug and play for standard functionality
• User-friendly operation through harmonized and clear operation at each
graphics hierarchy as well as clear operator philosophy
• Quick search from the operator point of view by means of plant view, aggregate
view, and data point view (structuring into different automation stations hidden
from the operator).
• Operator assistance through a common alarm display in each view
(plant, aggregate).
• SIMATIC Comfort panel with DESIGO-specific design and firmware
• Minimized engineering effort: System settings such as automation station IT
addresses and passwords for operation are entered on S7 TP700)
• Bus capable to operate and monitor several plants in different SIMATIC S7
CPUs
via MPI, Profibus DP, and Ethernet TCP/IP, and option to display plants,
aggregates, and individual data points in sequence from several CPUs, and
operate information points (e.g. set points, switching commands) as needed.
• Max. 4 Desigo S7 automation stations can be connected:
• Engineering data is saved for automatic start upon switch-on and return of
power. Automatic display of startup screen with plant view
• Password protection at several levels for operation
• Delivery in German and English
• Local operation logged in the management system (Desigo Insight) and
displayed on S7 TP700.
Function
The Touch Panel S7 TP700 applies a hierarchical operating philosophy:
• Startup window (all plants)
• Plant image (all aggregates or components of a plant)
• Aggregate image (all components of an aggregate).
• Data point screens
− Plant
− Characteristic curve (CHAR_LIN)
− Message (BI, MI)
− Measured value (AI)
− Controller (PID_CTR, CAS_CTR)
− Switching command (BO, MO)
− Setpoint (AVAL_OP, MVAL_OP, etc.)
− Positioning command (AO)
− Counter value (CI)