User Manual

2 / 6
Siemens Desigo S7 TP700 Touch Panel local HMI CM1N9290en_03
Building Technologies 2018-03-01
Application
Local operation and monitoring distinguishes itself through the following system
and product features:
Plug and play for standard functionality
User-friendly operation through harmonized and clear operation at each
graphics hierarchy as well as clear operator philosophy
Quick search from the operator point of view by means of plant view, aggregate
view, and data point view (structuring into different automation stations hidden
from the operator).
Operator assistance through a common alarm display in each view
(plant, aggregate).
SIMATIC Comfort panel with DESIGO-specific design and firmware
Minimized engineering effort: System settings such as automation station IT
addresses and passwords for operation are entered on S7 TP700)
Bus capable to operate and monitor several plants in different SIMATIC S7
CPUs
via MPI, Profibus DP, and Ethernet TCP/IP, and option to display plants,
aggregates, and individual data points in sequence from several CPUs, and
operate information points (e.g. set points, switching commands) as needed.
Max. 4 Desigo S7 automation stations can be connected:
Engineering data is saved for automatic start upon switch-on and return of
power. Automatic display of startup screen with plant view
Password protection at several levels for operation
Delivery in German and English
Local operation logged in the management system (Desigo Insight) and
displayed on S7 TP700.
Function
The Touch Panel S7 TP700 applies a hierarchical operating philosophy:
Startup window (all plants)
Plant image (all aggregates or components of a plant)
Aggregate image (all components of an aggregate).
Data point screens
Plant
Characteristic curve (CHAR_LIN)
Message (BI, MI)
Measured value (AI)
Controller (PID_CTR, CAS_CTR)
Switching command (BO, MO)
Setpoint (AVAL_OP, MVAL_OP, etc.)
Positioning command (AO)
Counter value (CI)