User Guide
9
Appendix
Shading Control
86
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
9.3.1 Operation
Circumstances by Outside Influences
Symbol
Operating
mode
BACnet-
Priority
Description
Scheduler 13 Schedulers normally write at the lowest priority
and can be overridden locally.
Blinds switch 7 A blinds switch that cannot be overridden by
the Management Station must be programmed
at priority 7 (for example, screening room).
13 Blinds switches that can be overridden locally.
Presence
detector
(occupied)
13 Presence detectors always report/switch at
priority 13; depending on the type, it is
switched either immediately or dependent on
the illuminance.
Presence
detector
(not occupied)
13 Presence detector always reports/switches at
priority 13.
Operation 13 Equal switching state as the local light switch.
Advanced
operation
8 Overrides the local setting until the switching
state is once again reset to
automatic
.
Central
functions
13 Equal switching state at priority 13 as by the
Management System.
8 Equal switching state at priority 8 as by the
Management System.
4 Wind strength exceeds the set limit value.
4 Wind strength is once again normal.
3 Servicing is being conducted.
3 Service work is finished.
Blinds
Raised
Displays blinds as per present operating state.
Automatic
mode
Displays blinds as per present operating state.
Blinds closed Displays blinds as per present operating state.