User Guide

9
Appendix
HVAC Room Control
78
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
9.1.1 BACnet Priorities for HVAC Applications
The following table illustrates the priorities used in Desigo.
Priorities in HVAC
Priority
Description
Example
1 Emergency mode 1
2 Emergency mode 2 Life safety (fan cannot be switched due to smoke)
3 Emergency mode 3
4 Protection mode 1
5 Protection mode 2 Locking via a dependent object (for example, the
damper must be opened before the fan can be switched
on).
6 Minimum on/off
7 Manual Operating
mode 1
8 Manual Operating
mode 2
Manual mode by system operator or on site
9‒12 Automatic mode 14
13 Manual Operating
mode 3
Manual operating in room
Manual operation by system operator
Scheduler
14 Automatic mode 5
15 Automatic mode 6 Automatic by program (for example, temperature
control)
16 Automatic mode 7