A6V10415564_en_a_21
Building Technologies 2015-06-23
5. Click Save .
The defined configuration is saved on the Desigo TRA room automation
station.
NOTE:
Use the filter function to limit the number of unassigned group members, for
example, 114 for group members of room number 114.
7.5.4 Removing Group Member Assignments
NOTICE
Loss of Data during Download with ABT Pro:
Edited group assignments are reset to the state of the last engineering data when
downloading from ABT Pro. Changes made by the Management System are lost
and can no longer be restored.
Present project data must first be imported back to ABT Pro.
Only then can the engineering data be re-downloaded with ABT Pro.
Desigo TRA project data is uploaded.
1. Select the desired category in the Management of Central Functions, from the
drop-down list box Group Categories.
Group master and group members are listed as per the selected category.
2. In the field Central Function with Assigned Member, select the group master.
3. Select one or more Group Members and click or remove assignment with
drag-and-drop.
Group member is no longer assigned to the group master.
4. Click Save .
The defined configuration is saved on the Desigo TRA room automation
station.
NOTE:
Unassigned members are automatically set to
Out of Service
.
7.5.5 Configuration Errors
Incorrectly configured group masters and/or group members are displayed in the
Configuration Error expander. Use the engineering tool to reconfigure the
application program.