5.1.5 Controlling Ventilation
During an emergency, the fire department can control ventilation using the
following operating modes:
Automatic
Emergency shutdown (lock)
Purge (supply air, extract air fan on, dampers, and VAV dampers open
Positive pressure
Negative pressure
1. In the System Browser, select Application View.
2. Select Applications > Logics > Central Functions > [Hierarchy Name] > HVAC
[Category] > [Emergency ventilation (CenEmgHvac)].
3. In the Contextual pane, click the Operation tab.
Displays emergency ventilation properties.
4. Select Command Value.
5. Click Manual.
6. In the Value drop-down list, select an option:
None
Emerg.off
Purge
Negative press.
Positive press.
7. Click Send.
The message Command successful is displayed.
NOTE:
An emergency command is executed at priority 2 or 3.