User Guide
5
Operating Central Function
Fire Department Emergency Functions
50
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
5. Click Auto.
6. Click Send.
The message Auto successful is displayed.
5.1.3 Switching on All Emergency Lighting for Multiple Zones
Emergency lighting on in multiple zones using Text Viewer
1. In the System Browser, select Application View.
2. Select Applications > Logics > Central Functions > [Hierarchy name] >
[Hierarchy 1-n] > [Central Functions for Emergency Lighting].
The associated lighting objects are displayed in the Text Viewer.
3. Click the Type column.
The list is sorted by type.
4. Highlight, using the <CTRL> key, all zones with type Control Function that
need to be switched on.
NOTE: In the Contextual pane, only properties that are the same as the
selected object display.
5. In the Contextual pane, click the Operation tab.
6. Select the Command value emergency property.
7. Click Manual.
8. In the Value drop-down list, select option On.
9. Click Send.
The message Manual successful is displayed.