User Guide
4
Emergency Lighting Control
Operating and Testing Emergency Lighting
46
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
8. Select Applications > Logics > Central Functions > [Hierarchy name] >
[Hierarchy 1-n] > [Central Functions for Emergency Lighting] > [Central
Function Emergency Lighting for Zone A (CenEmgLgt ZoneA)] > Emergency
Luminaire (EmgLmnr) > Command Emergency Luminiare (EmgLmnrCtl).
9. Drag the Emergency Light Object to the Action expander.
10. Define the following entries for the Emergency Light Object:
– In the Property property, select Present Value.
– In the column Command, select option Change [Write].
– In the column, Command, in the field Value, select option Start duration
test [3].
– In the column Initial delay enter a time in seconds [0 = immediate].
11. Select Applications > Reports > Status > [Test report].
12. Drag the Emergency Light Report to the Action expander.
13. Define the following entries for the Emergency Light report:
– In the Property property, select Not defined.
– In the column Command, select Execute.
– In the column Delay enter a time in seconds [18000 = 5 hours].
14. Click Save .
The test report is created once the executed reaction is finished.
Settings for Long Duration Test