4.4.4 Automatically Testing Group
When running tests, remember that there is no automatic feedback that the test is
finished or the battery is fully charged. For this reason, plan for sufficient reserve
time, to start the:
Test report group 1
Test group 2 (charging time for batteries for group 1)
13:00
Starting report
group 1
Test group 1
Charge time group 1
Test group 2
Charge time group 2
15.03.20xx
13:00
16.03.20xx
Starting report
group 2
Configuring Test Workflow
4.4.4.1 Creating Automatic Execution
The following description applies to a long duration with conducted once a year.
The example may need to be modified depending on the function selected and
project.
The test report is configured and the storage location defined.
1. In the System Browser, select Application View.
2. Select Applications > Logics > Reactions.
3. Open the Reaction Editor tab.
4. Open the expander Triggers.
5. Open the Time and Operating Mode expander and click Add.
6. Define the following entries:
From date
‒ Enter the create date.
To date
‒ Select checkbox
Any. No end date is defined.
Time
‒ Enter, under
Set start time the execution time 10:00:00.
‒ Clear checkbox
Set end time.
Effective days
‒ For
Recurrence, select Monthly.
‒ Selection the options
First, Sunday every 12 months.
7. Open the Output > Action expander.