Emergency Lighting Control
Operating and Testing Emergency Lighting
42
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
4.4.2.9 Enabling Switch-off Pulse
Switchable and dimmable devices that are not controlled by a local switch remain
in an emergency state after a function or continuous test. The command sets the
emergency state to
Off.
Central function Emergency Lighting and the corresponding group are
selected.
1. Select the Emergency Lighting Control Command.
2. In the Value drop-down list box, select option Switch-off pulse.
3. Click Change.
4.4.2.10 Creating Test Report
Three predefined reports are available to document conducted tests:
Function test
Short duration test
Long duration test
The Emergency Light reports are imported.
1. In the System Browser, select Application View.
2. Select Applications > Reports.
3. Open the Reports tab.
4. Select State and then one of the following reports:
– TRA Emergency Light Status Function
– TRA Emergency Light Status Short Duration
– TRA Emergency Light Status Long Duration
Hinweis: These are the standard reports and acquire all emergency
luminaires in the building. Create your own
Reports [➙ 43].
5. Click Execute .
The test report is generated.
6. Select Create and view PDF .
7. Click Print .
The test report is printed.
Example: Test report print out
NOTE:
The report displays state information in the language defined for the emergency
luminaires.