4.4.2.2 Starting Short Duration Test
The short duration test places the device in power outage state long enough to
calculate battery capacity without fully draining the battery.
Central function Emergency Lighting and the corresponding group are
selected.
1. Select the Emergency lighting control command.
2. In the Value drop-down, select option Start short duration test.
3. Click Change.
The short duration test starts .
The short duration test takes about 10 to 60 minutes depending on device
type
.
4. The test result must be read from emergency luminaires with a Report [➙ 42].
4.4.2.3 Starting Long Duration Test
The long duration test places the device in power outage state long enough to
measure battery capacity.
Central function Emergency Lighting and the corresponding group are
selected.
1. Select the Emergency lighting control command.
2. In the Value drop-down list, select option Start duration test.
3. Click Change.
The long duration test starts .
The long duration test takes about 1 to 5 hours depending on device type
.
4. The test result must be read from emergency luminaires with a Report [➙ 42].
4.4.2.4 Stopping Active Test
Stops a running function or running continuous test. A cancelled test must be
repeated within a defined period as per national standards.
Central function Emergency Lighting and the corresponding group are
selected.
1. Select the Emergency lighting control command.
2. In the Value drop-down list, select option Stop active test.
3. Click Change.