User Guide

4
39
Siemens Desigo TRA User Guide
A6V10415564_en_a_21
Building Technologies 2015-06-23
7. Click Send.
4.4.2 Manually Testing Group
The System Manager is in Operating mode.
The online connection is available.
1. In the System Browser, select Application View.
2. Select Applications > Logics > Central Functions > [Hierachy name] >
[Hierarchy 1-n] > [Central Functions for Emergency Lighting] > [Central
Function Emergency Lighting for Zone A (CenEmgLgt ZoneA)].
3. In the Contextual pane, click the Operation tab.
Displays emergency lighting properties.
4. Conduct the following actions:
Starting Function Test [ 39]
Starting Short Duration Test [ 40]
Starting Long Duration Test [ 40]
Stopping Active Test [ 40]
Overriding Rest Operating Mode [ 41]
Switching on Inhibit Operating Mode [ 41]
Switching off Inhibit Operating Mode [ 41]
Reset Hours of Operation [ 41]
Enabling Switch-off Pulse [ 42]
Creating Test Report [ 42]
NOTE:
A report of the previous test must be created before selecting another test type for
testing.
4.4.2.1 Starting Function Test
The function test briefly places the device in a power outage state. This test does
not impact battery capacity.
Central function Emergency Lighting and the corresponding group are
selected.
1. Select the Emergency lighting control command.
2. In the Value drop-down list, select option Start function test.
3. Click Change.
The function test starts .
The function test concludes after about one minute
.
4. The test result must be read from emergency luminaires with a Report [ 42].