User Guide

4
Emergency Lighting Control
Evaluating Test Report
38
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
4.3 Evaluating Test Report
A draft test report must be analyzed for possible faults in the emergency lighting.
The measures for a fault depend on the availability of additional emergency lighting
in this room.
Test Report
Evaluation of Test Report
4.4 Operating and Testing Emergency Lighting
Emergency lighting is generally switched on and off in groups. Individual tests can
be conducted manually for each emergency light.
The test workflow is as follows:
Test emergency luminaires
Create a report
Load battery before starting the next test
4.4.1 Switching On and Releasing Group
Emergency lighting can be switched on in advance if the time of the power outage
is known.
The System Manager is in Operating mode.
The online connection is available.
1. In the System Browser, select Application View.
2. Select Applications > Logics > Central Functions > [Hierarchy Name] >
Emergency Lighting [Category] > CenEmgLgt [Emergency Lighting
(CenEmgLgt)].
3. In the Contextual pane, click the Operation tab.
Displays emergency lighting properties.
4. Select the Emergency lighting control command.
5. Click Manual.
Emergency lighting is switched on at priority 8.
6. In the Value drop-down list, select an Option.