User Guide
3
Room operation as of V6
Selecting Room
32
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
The Advanced Operation tab displays the properties.
2. Select the Priority Matrix Room Operating Mode property and click Manual.
Displays the entry fields for Priority and Value.
3. In the Priority drop-down list, select option 08: Man.mode 2.
NOTE: In principle, any priority between 1-15 can be selected. Other BACnet
operator units also use priority 8 though. So that any BACnet operator unit can
reset the override to priority 8.
4. In the Value drop-down list, select the Operating mode:
– Comfort
– Economy
– Pre-Comfort
– Protection
5. Click Send.
The message Manual successful is displayed.
NOTE:
Successful operation only possible if you can write at a higher priority than is
displayed on the status bar for the
Priority Matrix
. You can, for example, overwrite
at the present priority 13 at 8, but not 7.
The display arrow indicates an active priority of 1 to 8. At priority 8, you can
change the Operating mode, for example,
Protection
to
Pre-Comfort
.