User Guide

3
31
Siemens Desigo TRA User Guide
A6V10415564_en_a_21
Building Technologies 2015-06-23
Text Group for Scenes
NOTE 1:
Texts added or changed on the Management System are not updated on the
room operator unit.
NOTE 2:
The
Maximum Value [ 31] must be modified on the scene object if the number
of scenes is changed. The maximum value is determined by the number of
scenes displayed in the
Value
drop-down list.
3.5.3.4 Modifying Maximum Value for Scenes
The Scene object [ 27] is selected.
1. Click Object Configurator tab.
2. Open the Properties expander.
3. Select the Present_Value property and then the Details expander.
4. In the Max text field, enter the corresponding number of defined scenes.
5. Click Save .
The scenes defined in the Text Group [ 30]
are displayed in the Value drop-
down list.
3.5.4 Override Operating Mode
The room is selected and room graphic is displayed.
1. In the room graphic, select Room > Room Operating mode.
A red frame is displayed when selected.