User Guide

3
Room operation as of V6
Selecting Room
30
Siemens Desigo TRA User Guide A6V10415564_en_a_21
Building Technologies 2015-06-23
8. Click Save .
The new or edited configuration is saved on the TRA room automation
station.
9. Test all scenes for functionality.
Scenes are tested and operate as per the requirements of each scene.
Object Assignment for Scenes
Example: Scene Configuration
ROpMod
Prio.
Light
Prio.
Blinds
Prio.
Fan
Prio.
Meeting Comfort 13 100% 7 Open 7 On 7
Presentation Comfort 13 30% 7 Close 7 On 7
Pause Protection 13 0% 13 Open 13 On 13
3.5.3.3 Editing Text Group
The Text Group is created during engineering data import and saved in the library
project folder. Texts are not available in the Management System if you define
other scenes; they must be created first.
The System Manager is in Engineering mode.
The Scene Object [ 27]
is selected and the Schedule tab is open.
1. In System Browser, select Management View.
2. Select Project > System Settings > Libraries > Project > Common > Common >
Texts > [Text group number].
3. Proceed as follows:
Change: Click the row and edit the text.
New text: Click Add new row :
a. In the column Value, enter a one-up number.
b. Enter a text for each language.
4. Click Save .
The Text Group is created.