User Guide

2
15
Siemens Desigo TRA User Guide
A6V10415564_en_a_21
Building Technologies 2015-06-23
Displays the room Operating mode properties.
3. Select the Value property and click Manual.
4. In the Value drop-down list box, select the Operating mode.
5. Click Send.
The message Manual successful is displayed.
In the Extended Operation tab the Present Priority and Priority Matrix changes
to 8 or 13.
NOTE:
Successful operation only possible if you can write at a higher
priority [ 77] than
is displayed on the status bar for the
Priority Matrix
. You can, for example,
overwrite at the present priority 13 at 8, but not 7.
The display arrow indicates an active priority of 1 to 8. At priority 8, you can
change the Operating mode, for example,
Protection
to
Pre-Comfort
.
2.3 Editing Setpoints
The room is selected and room graphic is displayed.
You can write a command at the Priority Matrix (see NOTE).
1. Select Settings > Setpoint Heating Comfort or Setpoint Cooling Comfort.
A red frame is displayed when selected and the most important values for
the setpoint are listed in the contextual pane of the
Operation tab.
2. Select the Operation tab.
The room setpoint properties are displayed.
3. Select the Value property and click Manual.