Data Sheet for Product

2
Siemens A6V12153307_en--_b
Smart Infrastructure 2022-02-18
Features
Built for rooftop unit control.
Operating temperature suitable for installing in rooftop unit enclosures.
Applications cover a wide array of single zone, constant and variable air options.
Fully programmable
Operational modes (Comfort, Standby, Economy, Protection, etc.).
Functions
The selected application and its parameters as well as input and output configuration
determine the primary automation station’s functionality. A detailed description of
functionality is available in the ABT (Automation Building Tool) online help.
Communication
2-Port Ethernet switch for cost-effective cabling via line topology.
USB connection for service and commissioning, firmware download, and LAN access.
The following functions are available with the KNX PL-Link bus:
Communication with room operator units, switches, sensors and actuators.
Plug-and-play connection of Siemens field devices with KNX PL-Link.
Integration of common devices using KNX S-Mode (ETS engineering required).
LED indication and Service button
LED color Activity Function
RUN Green Steady ON Device is ready for operation
Steady OFF Device is not powered
Regular flashing Start-up or the program is stopped
Red Steady OFF OK
Steady ON Program error
Communications error (KNX PL-Link)
Hardware fault
Rapid flashing Wrong or corrupt software
No application loaded
Blinking per wink command Physical device identification
2s
1s
5 Hz 5 Hz
2s
1s
SVC (Service
button)
-- Short press Physical identification on the network
-- Factory reset
1. Power off the device.
2. Power on the device.
3. Wait until the RUN LED lights up and
turns off again, then press the Service
button.
4. Keep the Service button pressed until
the RUN LED lights up, then release the
button. The device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED on, red
SVC LED flashes)