Data Sheet for Product
7
Siemens A6V12153309_en--_c
Smart Infrastructure 2022-02-18
Digital input (inputs X... or D...)
Contact query voltage Universal input: 18 V
Digital input: 21 V
Contact query current Universal input: 1.2mA, 7.4mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ
Outputs
The outputs are protected against short circuiting and incorrect wiring AC 24 V.
Analog (outputs Y10...Y40)
Type Range (over range) Resolution Output current
AO 0-10V 0...10V (0…10.5V) 2 mV Max. 1 mA
AO 0-10V standard 0...100%
0% = 0 V, 100% = 10V
(0...10.5 V)
2 mV Max. 1 mA
Switching outputs Triac (outputs Y1...Y8)
Type High side
The Triac closes the contact to AC 24 V
Switching voltage AC 24 V
Permissible load 250 mA / 6 VA per output (cos phi0.35)
Protection Short-circuit proof
Power supply for field devices (output V+)
Output voltage DC 24 V
Permissible load 100 mA/2.4 W
Protection against overload Short-circuit proof
Connections
Interfaces
MS/TP Interface type: RS485
Galvanic isolation: Yes
Baud rates: 9600, 19200, 38400, 57600, 115200 bps
Protocol: BACnet over MS/TP
Short-circuit proof protection against faulty wiring at max. AC
24V
USB (2.0) Plug: Type B
Data rate: 12 Mbps maximum, not isolated, short circuit
protected
KNX Type: KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Bus power: 50mA
Short-circuit proof, and protected against faulty wiring at max.
AC 24V