Data Sheet for Product

3
Siemens A6V12153309_en--_c
Smart Infrastructure 2022-02-18
Technical design
Power supply
The power supply provides controlled voltages for inputs and outputs. The primary
automation stations also supply DC 24V (max. 100mA) field supply. The supply is located
in the device to simplify wiring and diagnostics.
The processor controls the power supply. This ensures clean conditions for field devices
connected to the I/Os during startup, shutdown, and undervoltage.
Bus power supply
The primary automation station includes the bus power for KNX PL-Link. The bus power is
switched on by default, but can be switched off via web interface or configuration in the
Automation Building Tool (ABT).
The internal KNX PL-Link supply cannot be operated parallel to external power supplies. The
internal KNX PL-Link power must be switched off during the engineering phase for external
power. This is typically the case if the 50 mA from the internal supply is not enough to supply
all devices connected on the KNX PL-Link bus.
Type summary
The devices are supplied without terminal covers. The terminal covers must be ordered
separately. See Accessories.
Type Order number Description Inputs Outputs
DXP2.M18-110BR S55375-C107 DXP2.M18 Primary Automation Station 2DI, 4UI 8DO Triacs,
4AO 0...10V
Accessories
Type Order number Designation
DXA.H180 S55376-C120 Terminal cover for DXP.. 180 mm, 2 pieces
985-124 499Ohm Resistor Kit
Product documentation
Related documents such as the environmental declarations, CE declarations, etc., can be
downloaded from the following Internet address:
https://siemens.com/bt/download
Notes
Safety
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.