Catalog

Room automation Synco
Communicating controllers - RXL (Bus)
For fan coil‚ radiator‚ chilled ceiling
6-9
2015Some products are not available in every country
www.siemens.com/buildingtechnologies-productcatalog
Siemens Switzerland Ltd
Building Technologies Division
6
Operating voltage AC 24 V
Frequency 50/60 Hz
Power consumption 15 VA
Control algorithm PI
Digital inputs‚ number 2
Triac outputs ON/OFF
PWM
3-position
Triac output‚ switching voltage AC 24 V
Triac output‚ switching current 0.5 A
Relay output‚ switching voltage AC 250 V
Relay output‚ switching current 5 (4) A
Communication Bus
Room unit: PPS2
Service plug RXT20.1
Mounting location Ceiling voids with cover
Fan coil
Panel
Mounting On DIN rail
With screws
Dimensions (W x H x D) 113 x 167 x 62 mm
Room controller with bus communication
The controllers RXL2.. are used for temperature control in individual rooms.
- For 2-pipe with changeover or 4-pipe fan coil systems
- Control of thermic valve actuators AC 24 V‚ PDM‚ valve and damper actuators AC 24 V (3-position)
- Volt-free relay contacts for fan speed control
- Relay for electric heating (RXL22.1 only)
- Bus communication
- Connection to Desigo building automation and control system via PX KNX
- Commissioning with "Handy Tool" QAX34.3 or Synco ACS
Application description fan coil: CM110677
Application description RAD/CLC: CM110676
RXL2..
Product Title Triac outputs‚ num-
ber
Relay outputs‚ num-
ber
Data sheet Stock No. Product No.
Room controller for
3-speed fan
4 3 N3877 BPZ:RXL21.1/FC-10 RXL21.1/FC-10
Room controller for
3-speed fan
4 3 N3877 BPZ:RXL21.1/FC-11 RXL21.1/FC-11
Room controller with
3-speed fan and elec-
tric heating coil
2 4 N3877 BPZ:RXL22.1/FC-12 RXL22.1/FC-12
Room controller for
chilled ceilings and
radiators
4 0 N3878 BPZ:RXL24.1/CC-02 RXL24.1/CC-02
Range overview RXL2..
The application determines the usable actuator (PWM /3-position) with the triac output