Basic Documentation
7 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
2. Summary
2.1 Types
Product number Stock number Operating voltage Control outputs
Housing
color
3 pos ON/OFF DC 0..10 V
RDU341 S55770-T106 AC 24 V -- white
2.2 Ordering
∂ When ordering, please indicate both product no. / stock no. and name:
E.g. RDU341 / S55770-T106 room thermostat
∂ Order valve actuators separately
2.3 Functions
VAV systems via ON/OFF or modulating control outputs:
∂ Single-duct system
∂ Single-duct system with electric heater
The room thermostats are delivered with a fixed set of applications.
The relevant application is selected and activated during commissioning using one
of the following tools:
∂ Synco ACS
∂ ETS
∂ Local DIP switch and HMI
∂ Operating modes: Comfort, Economy (Energy Saving) and Protection
∂ Outputs for DC 0…10 V actuator and AC 230V electric heater (ON-OFF)
∂ Automatic or manual heating / cooling changeover
∂ Backlit display
∂ AC 24 V operating voltage
∂ Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
∂ Changeover between heating and cooling mode (automatic via local sensor or
bus, or manually)
∂ Selection of applications via DIP switches or commissioning tool (ACS700)
∂ Select operating mode via operating mode button on the thermostat
∂ Temporary Comfort mode extension
∂ Display of current room temperature or setpoint in °C and/or °F
∂ Display of outdoor temperature or time of day via KNX bus
∂ Minimum and maximum limitation of room temperature setpoint
∂ Minimum and maximum limitation of air flow signal DC 0...10 V
∂ Button lock (automatically or manually)
∂ 2 multifunctional inputs, freely selectable for:
– Operating mode switchover contact (keycard, window contact, etc.)
Use
Features
Functions