Basic Documentation

58 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
5.2.1 Parameter settings in ACS
In the ACS program, select Plant, then Open to open the plant.
To start the parameter settings, select Applications, then Plant engineering…::
The application and control parameters can be adjusted and downloaded.
Column Line no. contains the parameter number as shown in the parameter table.
Refer to section 3.12.
Some parameters have a different range in ACS than in the room thermostats.
The thermostat does not accept changes that are outside its range. This can be
observed online by the fact that a changed value jumps back to the original value.
To be sure, use the ranges described in the parameter tables in section 3.12.
STOP
Note!