4.3 Operation
See also Operating Instructions B3172 [2] enclosed with the thermostat.
Layout
1 Operating mode selector / Protection
2 Adjust setpoint and control parameters
User action Effect, description
Normal operation Actual operating mode and state are
indicated by symbols
Press any button
(thermostat in normal operation)
Backlit LCD turns on and… (see below for
further action)
After the last operation and a timeout of 20
seconds, the LCD backlight turns off
Press left button Change operating mode
Press left button (P01 = 2) Toggle between heating and cooling
Press left button while "Operating
mode" via bus is Economy
Activate "Extend Comfort mode"
(for details, see page 16)
Press left button >5 seconds Activate / deactivate button lock
Press + or – Adjusts the Comfort room temperature
setpoint .
Thermostat changes to Comfort mode
Press + and – >3 seconds, release,
then press + again >3 seconds
Go to parameter setting mode “Service
level”
Press + and – >3 seconds, release,
then press – again >3 seconds
Go to parameter setting mode “Expert
level”, diagnostics and test
Press operating mode button and “+”
simultaneously for 6 seconds
Enter (KNX) programming mode
Button operation