Basic Documentation

51 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
Parameter
Name Factory setting Range
Communications
P81 Device address
1)
255 1…255
P82 Geographical zone (apartment)
2)
--- ---, 1...126
P83 Geographical zone (room)
2)
1 ---, 1...63
P87 Air distribution zone --- ---, 1...31
P88 Transformation Precomfort 0 0 = Economy
1 = Comfort
1)
Physical address = Area.Line.DeviceAddress. Factory setting for Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2)
Type = geographical zone A.R.S. In RDG RDU sub zone = fixed value 1
Parameter
Name Range
Diagnostics & test
d01 Application number NONE = (No application)
Sd = Single duct
SdEL = Single duct with electric heater
d02 X1 state 0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00 = H/C Input shorted
100 = H/C Input open
d03 X2 state 0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00 = H/C Input shorted
100 = H/C Input open