Basic Documentation
49 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
3.12.3 Parameters of the "Service level"
Parameter
Name Factory setting Range
Service level
P01 Control sequence 1 0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
P02 Operation via room op selector 1 1 = Auto - Protection
2 = Auto - Comfort - Economy -
Protection
P04 Unit 0 0 = °C
1 = °F
P05 Measured value correction 0 K – 3 ... 3 K
P06 Standard display 0 0 = Room temperature
1 = Setpoint
P07 Additional display information 0 0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12h) (via bus)
4 = Time of day (24h) (via bus)
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Comfort setpoint minimum 5 °C 5 ... 40 °C
P10 Comfort setpoint maximum 35 °C 5 ... 40 °C
P11 Economy heating setpoint 15 °C OFF, 5 ... WCoolEco;
WCoolEco = 40 °C max
P12 Economy cooling setpoint 30 °C OFF, WHeatEco ... 40 °C;
WHeatEco = 5C min
P14 Button lock 0 0 = Unlocked
1 = Auto lock
2 = Manual lock
Parameter display depends on selected application and function.
Note: