Basic Documentation

48 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
3.12.2 Parameter setting / download via tool
Control parameters can be adjusted via bus either by parameter download during
commissioning or during normal operation with a tool like ACS.
With the ACS tool, the parameters can be changed…
during commissioning via parameter download (all parameters)
during normal operation via Popcard (most of the parameters)
Most parameters can be changed during normal operation using the OZW772 web
server or the RMZ792-B bus operator unit.
Only the parameters for device address can be downloaded via ETS3 Professional.
This is to simplify and avoid a conflict.
It allows you to further engineer communication objects of an RDU previously
commissioned vial local HMI or ACS (assigning communication objects to group
addresses).
The basic application can only be changed via parameter download with ACS.
The RDU KNX thermostats require version ETS3f or higher / ACS version 5.11
or higher.
Connecting a KNX commissioning / operating tool to the RDU is described in
section 4.2.
ACS
OZW772 Web server,
RMZ792-B
bus operator
unit
ETS
Notes:
Connecting a KNX tool