Basic Documentation

39 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
3.10.4 Example of heating and cooling demand zone
The building is equipped with Synco controls on the generation side and RDU /
RDG thermostats on the room side.
RMH760 RMH760 RMB795
Konnex TP1
RDG...RDU...
RDF...
T
T
T
T
1
2
P3171Z01
Heat requistion
Heat demand
Heat distr zone 1
Heat source
Controller 1 Controller 2
Controller 3
Controller 4 Controller 5 Controller 6
Controller 1 Controller 2 Controller 3 Controller 4 Controller 5 Controller 6
Heating circuit
fan coil
Fan coil
room A
VAV box
room B
Fan coil
room C
DHW heating
Heat demand
Heat demand
Heat demand
Heat demand
Heat requistion
Heat distr zone
source side: 1
Heat distr zone 2
Heat distr zone 2 Heat distr zone 2
Heat distr zone 2
Setting values
MV MV
T
T T
In the case of a typical application, the individual RDU / RDG room thermostats –
when used with the RMB975 central control unit – signal their heat demand directly
to the primary controller (in the above example to the RMH760).
(1) and (2) designate the numbers of the distribution zone.
This type of application can analogously be applied to refrigeration distribution
zones
If no 2-pipe fan coil is used, heat and refrigeration demand signals are sent
simultaneously to the primary plant
Explanation relating to
the illustration
Notes: