Basic Documentation

37 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
RDU
Air handling unit
Sensor
Outside temperature zone 1
Air distr zone 1
Geogr. zone 2.5.1
Air demand
Outside temperature
3172Z02en
Outside temperature
Air demand
Outside temperature zone 1
Air distr zone 1
Time Switch
Operating mode Operating mode
Geogr. zone 2.5.1 or 2.1.1
Room temperature
For a detailed description of KNX (topology, bus supply, function and setting of
LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco
700, 900 and RXB/RXL, Basic Documentation" [6]
LTE mode data points and settings are described in the Synco Application
Manual [12]
To engineer and commission a specific system, use the Synco700 planning and
commissioning protocol (XLS table in HIT, [7])
3.10.3 Zone addressing in LTE mode (in conjunction with
Synco)
In cases where RDU KNX room thermostats are used in LTE mode (e.g. in
conjunction with Synco), zone addresses need to be allocated.
The following zone address must be defined together with the Synco devices at the
planning stage depending on the application.
Short description Factory setting Parameter
Geographical zone (apartment) --- (out of service) P82
Geographical zone (room) 1 P83
Air distribution zone --- (out of service) P87
Note: “Subzone” of “Geographical zone” is fix 1 (not adjustable)
The device will send and receive LTE communication signals only if the zone
address is valid (not OSV = out of service).
Engineering and
commissioning