Basic Documentation

35 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
# Function of
input
Description Type
X1/X2
KNX
R
Fault
information
6 Fault Digital input to signal an external fault (example: dirty air
filter).
If the input is active, “ALx” is displayed and a fault is
sent on the bus. See also section 3.10.11.
(Alarm x, with x = 1 for X1, x = 2 for X2).
Note: Fault displays have no impact on the thermostat's
operation. They merely represent a visual signal.
DI
KNX
R
X1, X2
(Digital)
7 Monitor input
(Digital)
Digital input to monitor the state of an external switch via
bus.
DI
KNX
R
X1, X2
(Temp.)
8 Monitor input
(Temperature)
Sensor input to monitor the state of an external sensor
(e.g. QAH11.1) via bus.
AI
Operational action can be changed between normally open (NO) and normally
closed (NC) via parameter P39, P41.
Each input X1, X2 must be configured with a different function (1…5).
Exception: 1 or 2 inputs can be configured as fault (6) or monitor input (7,8)
X1 is factory-set to “Operating mode switchover” (3), X2 to “External sensor”
(1)
For more detailed information, refer to section 3.4.