Basic Documentation
30 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
3.6.5 Single-duct with electric heater
General rule: In case of insufficient air flow, the thermostat cannot protect the
electric heater against overtemperature. Therefore the electric heater MUST
feature a separate safety device (thermal cutout).
On single-duct applications with electric heater, the thermostat controls a valve plus
an auxiliary electric heater. Parameter P01 is not available.
The output signal for the air flow can be limited to a minimum and maximum value
if required using parameters P63 and P64. With application " Single-duct with
electric heater", the min. value of P63 is overridden, so that the air flow never drops
below 10 % while the electric heater is ON.
The air flow starts to rise depending on the acquired room temperature, the current
supply air temperature (if available) and the setpoint.
The electric heater receives an ON command when the acquired room temperature
drops below setpoint (= setpoint for electric heater).
Remote enabling / disabling of the electric heater is possible via input X1 or X2 for
tariff regulations, energy savings, etc.
Input X1 or X2 must be commissioned accordingly (parameters P38, P40).
See section 3.8.
The electric heater can also be enabled / disabled via bus.
If “Enable electric heater” input is used via bus, then the function must not be
assigned to a local input X1 or X2.
On start-up of the controller and if the primary controller sends the information that
the primary fan is off, the thermostat disables the electric heater, see section
3.10.9.
To avoid overheating of an electric heater when switched off, the air flow signal of
Vmin must be maintained for a preset "fan overrun time" (P54, factory setting
60sec).
In conjunction with a Synco primary controller it will be assured that the primary fan
keeps running during the fan overrun time.
See also section 3.10.10.
Caution
Electric heating, active in
cooling mode
Digital input “Enable
electric heater”
KNX
R
Enable electric heater
Note
"Fan overrun time"