Basic Documentation

27 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
The state (heating or cooling) of the thermostat can be monitored with the ACS tool
(diagnostic value “Control sequence”). The last active mode is displayed when the
thermostat is in the dead zone or temperature control is disabled.
With a single-duct application, the control sequence state is determined by the
application mode (see section 3.6.2) and by the state of the heating / cooling
changeover signal (via local sensor or bus), or fixed according to the selected
control sequence (P01 = heating (0) / cooling (1)).
Application
mode (via bus)
State changeover / conti-
nuous heating or cooling
Control sequence state
Auto (0)
Heating Heating
Cooling Cooling
Heat (1), (2), (8) Heating Heating
Cooling
Heating
Cool (3), (5)
Heating
Cooling
Cooling Cooling
Night purge (4),
Fan only (9)
Heating Heating
Cooling Cooling
With applications "Single duct with electric heater / radiator / heating / cooling coil",
the control sequence state depends on the application mode and on the heating /
cooling demand.
Application
Mode (via bus)
Heating / cooling demand Control sequence state
Auto (0)
Heating Heating
No demand Heating / cooling depending
on last active sequence
Cooling Cooling
Heat (1), (2), (8)
Heating Heating
No demand
Heating
Cooling
Heating
Cool (3), (5)
Heating
Cooling
No demand
Cooling
Cooling Cooling
Night purge (4),
Fan only (9)
No temperature control active Heating / cooling depending
on last active sequence
The value of the output as a function of the room temperature is shown in the
following diagram in case of a heating and cooling system:
0
TR
Wheat Wcool
100%
0 = Cool
1 = Heat
3171D01
Wheat = current heating setpoint
Wcool = current cooling setpoint
ACS Operating
Heating OR cooling
Heating AND cooling