Basic Documentation

20 / 68
Siemens RDU341 Basic Documentation CE1P3172en
Building Technologies 2017-02-17
If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control
the room temperature in the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in
heating mode or risk of overtemperature in cooling mode!
The Economy setpoints are accessible at the service level (P11, P12); the
Protection setpoints at the expert level (P65, P66).
3.3.2 Setting and adjusting setpoints
Room temperature setpoints can be
set during commissioning
adjusted during runtime
The source can be
the local HMI
a tool
a central control unit
The thermostat stores the setpoints
in EEPROM in the form of parameters
in the runtime memory
The table below shows the interrelations:
Setpoint setting
Stored in EEPROM
of thermostat
Commis
sioning
– HMI
– Tool download
Input LTE mode
Input S
-
m
ode
Comfort basic setpoint
Dead zone Comfort 1)
Setpoints Heating
Setpoints Cooling
Comfort basic setpoint P08 Comfort basic setpoint
P33 Dead zone Comfort 1)
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoints Heating
Setpoints Cooling
P11 Economy Heating
P12 Economy Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
P65 Protection Heating
P66 Protection Cooling
Current
runtime
setpoints in
thermostat
Setpoint
adjustment
New
current
runtime setpoints
in thermostat
Input LTE mode
2)
Input S
-
m
ode
3)
Local ope
-
ration 3)
Comfort setpoint Setpoint shift H
Setpoint shift C
Comfort setpoint + / - buttons Comfort setpoint
Economy Heating
Economy Cooling
Setpoint shift H
Setpoint shift C
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
Protection Heating
Protection Cooling
Effective room operating mode Current setpoint (used by the thermostat for temperature control)
Caution
KNX
R
Comfort basic setpoint
Comfort setpoint