Room-supply air temperature cascade and humidity controlRMU730B..
AEFB01 U3B HQ
V 7-day time switch with holiday / special day program
V Control of a 2-speed fan
V Control of the supply air temperature via the mixed air dampers‚ the heating
coil valve and cooling coil valve in sequence
V Control of room humidity via the air humidifier (on command and modulating
positioning signal)
V Frost protection with frost protection monitor
V Supervision of the supply and extract air fans with differential pressure sen-
sors
V Supervision of the supply air filter with a differential pressure sensor
V Limitation of supply air humidity
The indicated energy efficiency classification can be attained only if the fol-
lowing functions are implemented:
V Air flow control at the room level‚ demand control (Air quality sensor
required)
V Air flow control at the air handler level‚ automatic flow or pressure control
with or without pressure reset (Automatic fan step switching corresponds to
Efficiency Class B / Step 2 must be switched based on air quality)
V With heat exchanger overheating control
V Free mechanical cooling (Outside air temperature and room temperature sen-
sor required)
V Supply Temperature control‚ variable set point with load dependant compen-
sation
V Room or exhaust air humidity control
To fulfill the classification‚ the plant must be equipped with
all indicated functions.
Room-supply air temperature cascade and humidity controlRMU730B..
ADFP01 U3B HQ
V 7-day time switch with holiday / special day program
V Control of a 2-speed fan
V Control of the supply air temperature via the heat recovery system‚ the heat-
ing coil valve and cooling coil valve in sequence
V Control of room humidity via the air humidifier (on command and modulating
positioning signal)
V Frost protection with frost protection monitor
V Supervision of the supply and extract air fans with differential pressure sen-
sors
V Supervision of the supply and extract air filters with differential pressure sen-
sors
V Limitation of the supply air humidity
The indicated energy efficiency classification can be attained only if the fol-
lowing functions are implemented:
V Air flow control at the room level‚ demand control (Air quality sensor must be
integrated as an additional feature)
V Air flow control at the air handler level‚ automatic flow or pressure control
with or without pressure reset (Automatic fan step switching corresponds to
Efficiency Class B / Step 2 must be switched based on air quality)
V Heat exchanger defrost control (Exhaust air temperature sensor required)
V With heat exchanger overheating control
V Free mechanical cooling (Outside air temperature and room temperature sen-
sor required)
V Supply Temperature control‚ variable set point with load dependant compen-
sation
V Room or exhaust air humidity control
To fulfill the classification‚ the plant must be equipped with
all indicated functions.