User Manual
11
3.2.5 Adapting parameter values form the building model
used by predictive heating control
Advantages:
– Successful adaptation of the building model increases comfort
– Sound control response at narrowly dimensioned heating output
– Excellent control response between boost heating and comfort mode
The parameter values of the building model are continuously adapted during
operation (automatic adaptation) by processing the measured values for outside
temperature, room temperature, flow temperature as well as using the recirculated
pump's feedback message.
In addition to adapting static building model paramters (i.e. heating curve
parameters), predictive heating control also continuously adapts the dynamic
building model parameters to real building performance during operation.
3.2.6 Preventing general heating mode based on predictive,
model-based calculation
Advantages:
– Reduces the operating hours of the circulating pump
– Reduces heat loss in the piping network
– Reduces heat loss at generation
Thanks to the building model, predictive heating control calculates the comfort
deviations to be expected when heating is off. If these comfort deviations are
acceptable, general heating mode is prevented or locked. The deviations are
calculated for at least the next 64 hours. Acceptable comfort deviations are set by
predictive heating control and cannot be changed.
3.2.7 Mixing circuit flow temperature control with modulating
valve and pump
Advantages:
– Automatic flow temperature setpoint adjustment at poor flow temperature control
The flow temperature is controlled with the aid of a modulating valve and
recirculated pump. A PI controller is used for conventional control. The predictive
heating controller automatically corrects the flow temperature setpoints if control is
poor for whatever reason (e.g. poorly set control parameter).