Commissioning Instructions
Workflows
Tool-free commissioning of an operating and monitoring system
4
57 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
4.4.1.6 Updating the touch panel settings (PXM… touch panel only)
This procedure sets the screen orientation, defines the default graphic that should display after a power cycle
and sets up Favorites that can be accessed through the touch panel.
CAUTION
Minimize links to external URLs. Linking to external URLs, such as Favorites,
Web cams and external Web services poses a security risk.
● URLs shall only direct to secure services, such as Web servers hosted by
devices in the building automation control network. Using touch panels for
applications other than building automation, for example, to display a news
Web site, exposes your system to the risk of downloading and executing
malicious scripts.
● The system integrator is responsible for making a risk-benefit decision about
providing external URLs and for informing the customer of potential risks.
Complete this procedure in ABT-SSA.
1. Select > Favorite commissioning > Touch panel settings.
2. Click to display all properties.
3. Screen orientation
Select a defined value for the Screen orientation and click OK.
NOTICE! If the device loses power before you have logged out, the orientation setting is not saved.
4. Home URL
Select Home URL, enter the URL for the default graphic that should display on the touch panel after a
power cycle and click OK.