Commissioning Instructions
Workflows
Tool-free commissioning of an operating and monitoring system
4
54 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Application fields
Figure 14: Commissioning wizard, Application fields.
Setting
Description
Application template description
If the device contains multiple applications, select the Application type from the drop-down list.
Active system language
User interface language for the application.
Default: The language selected on the login page.
Object naming convention
Naming format of the BACnet objects. Only Hierarchical, standard names apply for Desigo
Control Point.
● Hierarchical, standard names (default)
Hierarchical naming concept where names are made up of room, room segment, etc. For
example, %R%'RHvacCoo'TCtlC'SpCCmf, where SpCCmf (cooling setpoint for comfort) is
the BACnet object.
● Abbreviated, standard names
Flat naming concept using only object names. For example, CMF CLG STPT. The
abbreviated name displays only for those objects defined in the library. (An abbreviated
name is not defined for all objects.) Otherwise, the hierarchical name displays.
Note
This option does not apply for Desigo Control Point.
● Local naming convention
User-defined names for the objects.
Note
This option does not apply for Desigo Control Point.
Table 9: Application fields.
4.4.1.3 Configuring language support
If a Desigo Control Point device is used in combination with Desigo or Apogee controllers, you must configure
the Desigo Control Point device for languages that require special symbol tables.
Configuring language support
1. Select > Favorite commissioning > [operating and monitoring device].
2. Click to display all properties.
3. Scroll down to select the desired Supported character set (Apogee or Desigo).
4. Select the appropriate character set from the drop-down list and click OK.
The special character set is now supported by Desigo Control Point.