4.4 Tool-free commissioning of an operating and monitoring system
Use the workflow in this section to configure and commission a Desigo Control Point operating and monitoring
device and the Operation application.
Note
This workflow includes a basic procedure for integrating data points in the Operation application. For information
on working with integration templates and advanced functions, see the
Desigo Control Point Engineering
Manual
(A6V11211560).
Commissioning Step
1
Configuring the operating and monitoring device [➙ 51]
2
Subscribing to the time master [➙ 59]
3
Configuring for kiosk graphics on a touch panel [➙ 60]
4.4.1 Configuring the operating and monitoring device
Configuration of the operating and monitoring device includes the following procedures:
● Performing the initial login [➙ 51]
● Using the Commissioning wizard [➙ 52]
● Configuring language support [➙ 54]
● Assigning devices to the operating and monitoring device [➙ 55]
● Enabling Secure HTTP communication [➙ 56]
● Updating the touch panel settings (PXM… touch panel only) [➙ 57]
● Subscribing to the time master [➙ 59]
● Time synchronization of the time master [➙ 59]
4.4.1.1 Performing the initial login
Use the appropriate initial login procedure for your configuration:
● Initial login to a PXM operating and monitoring device using the touch panel
● Initial login using the embedded Web server and a standard Web browser
ⓐ Initial login to a PXM operating and monitoring device using the touch panel
The touch panel is ON and a network cable is connected.
1. Tap the Orientation icon to select a screen orientation and then tap .
The Desigo Web login page displays.
ⓑ Initial login using the embedded Web server and a standard Web browser
1. Connect to the USB port of the operating and monitoring device.
2. Type the IP address 192.168.250.1 in the address bar of a browser.
The Desigo Web login page displays.