4.2 Change values
Procedure
1. Do one of the following to open the ABT-SSA Web server component:
– In ABT Site, select Startup > Configure and download, and click Go online.
– In supported devices, access the device directly through any standard Web browser.
Accessing the ABT-SSA interface [➙ 6]
2. Enter your login credentials if prompted.
The ABT-SSA work area displays.
3. Click the Main menu button and select Application (if not your default view).
The Application work area displays.
Note
The Favorites and Events work areas display a subset of objects that can be changed, as well.
4. Select the desired room and click List View to see all objects associated with that room.
5. Select an accessible object to change its current state or value.
Note
Some objects are accessible by clicking on them and will cascade to reveal an operating element.
State indicators identify the current condition of the objects associated with the room.
State indicators [➙ 17]
4.3 Balancing
Use this procedure for balancing the system.
Procedure
A communication connection to the automation station is established.
For more information, see the ABT Site help.
1. Do one of the following to open the ABT-SSA Web server component:
– In ABT Site, select Startup > Configure and download, and click Go online.
– In supported devices, access the device directly through any standard Web browser.
Accessing the ABT-SSA interface [➙ 6]
2. Enter your login credentials if prompted.
The ABT-SSA work area displays.
3. Click the Main menu button and select Application (if not your default view).
The Application work area displays.
4. From List view, click Room segment [x] > Hvac > Supply air VAV > Supply Air VAV device mode and
select/verify that the current value = Control mode, and click OK.
5. Select Favorites > Favorite Balancing view.
Note
Depending on the state of the tool, the sequence may be Favorites > Room segment [x] > Favorite
Balancing view.
The automation station calculates a new flow coefficient and continuously displays updating object
values.