Commissioning Instructions

ABT-SSA (Setup & Service Assistant)
Assigning devices to an operating and monitoring device
2
42 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Setting
Description
Discovery scope
Determines if the device discovery is restricted to the local network or if remote networks are
included.
Options: Local network or Remote network.
If Remote network is selected, verify that the Network number setting is correct.
Network number
The network number to use for the device discovery.
Max. device instance number
Min. device instance number
Limits the device discovery to a range of devices.
The maximum value is 4194302. The minimum value is 1.
Include 3rd party devices
Determines if third-party devices are included in the device discovery.
Select No to exclude third-party devices, or Yes to include third-party devices.
Command
Issues a Discover command using the modified parameters.
Note: The message No items displays while responses from the network are being processed.