Commissioning Instructions

ABT-SSA (Setup & Service Assistant)
Assigning devices to an operating and monitoring device
2
40 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Field
Description
Local date
Current date in DD.MM.YYYY format. This information can be modified through the device
Properties in ABT-SSA.
Local time
Current local time in HH:MM:SS format. This information can be modified through the device
Properties in ABT-SSA.
Max APDU length accepted
Specifies the maximum length of the APDU. For example, BACnet/IP.
Number of APDU retries
Specifies the number of retries from 1 through 5. The default is 3. This information can be modified
through the device Properties in ABT-SSA.
APDU segment timeout
Specifies the amount of time in milliseconds between retransmission of an APDU segment. The
suggested value is 5000.
APDU timeout
Specifies the timeout value in milliseconds from 1000 through 10000. The default is 3000. This
information can be modified through the device Properties in ABT-SSA.
Max segments accepted
The maximum number of octets that may be contained in a single, indivisible application layer
protocol data unit. The value of this property is greater than or equal to 50. For example, 32.
Segmentation supported
Indicates whether the BACnet device supports segmentation of messages and, if so, whether it
supports segmented transmission, reception, or both. For example, Segmented both.