Commissioning Instructions

ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
38 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Click to display or hide the ABT-SSA Setup & service menu.
Clear device
Stops and clears the device and clears the application configuration.
If the Tool-free commissioning workflow is
always
used to configure the device and application, the following apply after a
clear device is performed:
The factory-loaded application is available on the device
The factory-loaded application can be activated through the Tool-free commissioning workflow.
If ABT Site is used
at any time
to configure the device and application, the following apply after a clear device is performed:
The factory-loaded application is not available on the device.
ABT Site must be used to configure the device and application.
Clear application
Stops the device, clears the application configuration, and keeps the existing device configuration. The device must be
configured. The loaded application remains on the device and can be activated.
Field
Description
Object name
Name of the device. For example, AS_4.
Model name
Device model. For example, PXG3.W200-1.
Local date
Current date in DD.MM.YYYY format.
Local time
Current local time in HH:MM:SS format.
System status
Current status of the system. Default is Operational.
Firmware revision
Current firmware loaded into the device. For example, FW=02.10.28.94;WPC=1.5.4;SVS-
300.1:SBC=13.21;
Serial number
The serial number of the physical device.