Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
34 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Testing I/O bus data points
The I/O bus > Data point test view allows you to test data points from the configured I/O bus and log the results.
The data point test carries out On/Off/Multistate, and setpoint commands.
Testing I/O bus data points
1. Click (overwrite with priority=8).
The icon changes to . Manual operation with and is enabled.
2. Click or .
AO: The positioning value is increased or reduced in increments of 10.
BO: The switching value is changed.
MO: The stage value is increased or reduced.
BlsOut: (+) blinds up; (-) blinds down.
3. Click to release the overwrite.
Notes
● The symbol indicates a faulty value. The tooltip contains the cause (out of service or alarm).
● DXR2 devices: To identify the module and the channel on the on-board socket, see the data sheet.
DXR2.. Pins and addresses [➙ 62]
Commanding at priority=1
WARNING
Commanding at priority=1 ( ) overrides life/plant safety functions!
Overwriting the priority or using incorrect values may trigger system malfunctions
which may result in injuries or property damage.
● Use commanding at priority=1 ( ) only if you can check the consequences.
● Release overwritten values as soon as possible. Click to release
overwriting.
Note: