Testing DALI data points
The DALI bus > Data point test view allows you to test data points from configured DALI devices and log the
results (state, comment). Point test carries out On/Off and dimming (%) commands.
Switch or dim DALI data points
1. Click (overwrite with priority=8).
The icon changes to . Manual operation with and is enabled.
2. Click or .
The DALI device is switched on or off (100%, 0%), or dimmed (60%).
The dimming value is increased or reduced at 10% increments.
3. Click to release overwriting.
Note: The symbol indicates a faulty value. The tooltip contains the cause (out of service or alarm).
Commanding at priority=1
WARNING
Commanding at priority=1 ( ) overrides life/plant safety functions!
Overwriting the priority or using incorrect values may trigger system malfunctions
which may result in injuries or property damage.
● Use commanding at priority=1 ( ) only if you can check the consequences.
● Release overwritten values as soon as possible. Click to release
overwriting.
Note:
● A higher priority (1-7) must be active to command at priority=1 ( ).
● If priority=1 ( ) is active then a simultaneous active priority=8 ( ) can be released but NOT be reenabled.
Logging test results
1. Click to display the State drop-down list for the point being tested.
2. Select the applicable test result from the drop-down list. (Failed or Passed).
3. Do one of the following: