Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
24 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
1. Click Stop.
2. Click either All lamps on, All lamps off or All lamps blinking.
The switching status remains active until another function is selected, or until the DALI bus is restarted.
3. Select Run.
This stops the command test and starts the DALI bus.
Note
This function can also be run using the service pin on the PXC3..A.
Automatically addressing DALI devices (short address)
1. Click Auto addressing.
The DALI bus is scanned. The alongside the button displays ongoing auto addressing and may take
a few minutes (depending on the number of DALI devices).
All discovered DALI devices receive a DALI bus short address. Existing DALI bus short addresses
remain as-is.
Auto addressing does not update the contents of the DALI identification and DALI data point test Web
pages.
2. Check result. Select Identification in the left navigation pane.
Following auto-addressing, the Web page DALI identification shows the DALI bus short address and the
detected DALI device type (device online) in the Online list.
Note
If any installed DALI devices are not discovered (that is, DALI V0 device), use Reset all electr. control gears to
clean all short addresses and old configurations in all DALI devices (factory reset).
Reset all DALI control gears to the factory setting
This may be used to clean up a test configuration or to resolve problems.
The command Reset all electr. control gears deletes the short address and the configuration parameter in all
DALI control gears on the DALI bus.
1. Click Reset all electr. control gears.
2. Click Auto addressing.
3. Assign DALI devices.
Be aware, before downloading the engineered data again, make a readback of the onsite configuration data
(default option).