Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
23 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Reset the DALI bus
⚫ Click Reset.
All DALI devices are reinitialized (runtime configuration, bus configuration).
The DALI bus is restarted, and the status is displayed as Operational.
Start/stop the DALI bus
⚫ Click the Stop/Run toggle button.
The DALI bus is started or stopped, and the status is updated (Operational or Stopped).
Disable internal power supply
Enabled internal power supply is the standard use case. To operate with disabled internal power supply some
additional engineering settings are needed. Otherwise it causes a communication error.
Executing a command test
The command test is used to switch all connected DALI devices to ON, OFF or FLASHING.
The DALI bus must be stopped. Only then are the commands All lamps on, All lamps off or All lamps
blinking active.
CAUTION
The "Blink all" function may damage lights.
Verify that lights, whose lifetime is impacted by blinking, are properly connected.
This is required for all lights connected to the DALI bus of this automation station.