Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
22 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Device and network configuration properties
Field
Description
Host name
Host name label. For example, AS1.
Object name
Name of the device. For example, AS_4.
Description
A string of printable characters whose content is not restricted. A description may be selected from
the text picker. For example, Automation station.
Model name
Automation station model. Assigned by the vendor to represent the model of the BACnet device.
For example, PXC3.E75A.
System status
Current status of the system. Default is Operational.
Operation URI
Web address of the device. For example, http://192.168.251.4.
Serial number
Lists the serial number of the physical automation station associated with the BACnet device
object.
Firmware revision
Current firmware loaded into the device. For example, FW=01.20.43.1080;WPC=1.2.1080;SVS-
300:SBC=13.20
Application SW version
The version of the application software installed in the automation station. The content of this
string is a local matter, but it could be a date-and-time stamp, a programmer's name, a host file
version number, etc. For example, Sep_29_2014_19_44_54.
Local date
Current date in DD.MM.YYYY format.
Local time
Current local time in HH:MM:SS format.
Max APDU length accepted
Specifies the maximum length of the APDU. For example, BACnet/IP.
Number of APDU retries
Specifies the number of retries from 1 through 5. The default is 3.
APDU segment timeout
Specifies the amount of time in milliseconds between retransmission of an APDU segment. The
suggested value is 5000.
APDU timeout
Specifies the timeout value in milliseconds from 1000 through 10000. The default is 3000.
Max segments accepted
The maximum number of octets that may be contained in a single, indivisible application layer
protocol data unit. The value of this property is greater than or equal to 50. For example, 32.
Segmentation supported
Indicates whether the BACnet device supports segmentation of messages and, if so, whether it
supports segmented transmission, reception, or both. For example, Segmented both.
2.4.1.3 DALI bus
DALI bus state and auto addressing
The DALI bus > State view summarizes the status of the DALI bus and allows you to start/stop the bus, disable
the internal power supply and automatically address DALI devices discovered on the network.
DALI bus State procedures
To perform the procedures in this section, select DALI bus in the command bar and State in the left navigation
pane.