Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
21 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Release overwrite
1. Check the data point test Web page for each bus to ensure that you want to remove all overwritten data
points.
Testing DALI data points [➙ 28]
Testing KNX PL-Link data points [➙ 30]
Testing I/O bus data points [➙ 34]
2. Click Prio 1 or Prio 8.
All overwritten states of the respective priority on this automation station are removed.
No new commands are issued. The set values remain until the next program command.
The overwrite indicator is removed.
2.4.1.2 Overview: Details
The Overview > Details view allows you to view all the device properties of the automation station based on its
BACnet Device object.
All entries are executed directly in ABT-SSA and regularly saved every 15 minutes in non-volatile memory on
the automation station. It is immediately saved with Save and log out. No data is saved on the commissioning
computer.