Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Installation
2
20 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
① Device and network configuration
Displays a summary of the automation station.
Object name
Name of the device. For example, AS_4.
Model name
Device model. For example, PXC3.E75A.
Local date
Current date in DD.MM.YYYY format.
Local time
Current local time in HH:MM:SS format.
System status
Current status of the system. Default is Operational.
Firmware revision
Current firmware loaded into the device. For example,
FW=01.20.43.1080;WPC=1.2.1080;SVS-300:SBC=13.20
Serial number
Serial number of the physical device.
② Start/stop the automation station
Program state displays the current state of the application program. The options are Running or Halted. Default
is Running.
Stop/Run toggle button
Stops or starts the application program on the automation station
Note
If you cannot start the automation station via Run, restarting using
network off/on may be possible.
③ Clear the automation station
Use the following buttons to clear the device or the application:
Clear device button
Stops the device, clears it, and clears the application configuration.
The loaded application remains on the device and can be activated. The
device must be configured.
Clear application button
Stops the device, clears the application configuration, and keeps the
existing device configuration. The device must be configured.
The loaded application remains on the device and can be activated. The
device must be configured.
④ Bus state summary
A list of the connected field buses and the following information for each bus:
● Bus operating state
● Number of engineered devices that are connected
● Number of configured devices
● Reliability state
● Overwrite summary for the field bus. The status is Yes if at least one data point is in the overwrite state.
⑤ Release overwrite
Releases all overwritten data points on the automation station with a single command.
● Buttons in the Remove overwrite section are active when at least one data point is in the corresponding
overwrite state.
● The overwrite indicator shows the number of data points in the corresponding overwrite state.
● Selecting a button removes the corresponding overwrite state for all data points on this automation station.
Release overwrite [➙ 20]
Release overwrite
This procedure releases all overwritten data points on the automation station with a single command.