Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Device, Field buses, Application
2
17 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Indicator
Description
BACnet object type
Trend log
TrndLogS
Other special Objects
AppCnf, CmnEvt, DevObj, FileObj, FldBusMgmt, NotifClass,
NwkPortIP, NwkPortMSTP, Pgm
System function objects
Diagnostics
Diag
Event log
EvtLog
Calendar
Calendar
Scheduler
Schedule
2.3.5 State indicators
The Desigo state indicator icons represent the current condition of functions and/or objects associated with a
room.
Indicator
Description
Cause
Value quality
Fault
Indicates a system or process alarm
Transition
Indicates a non-alarm event (object not updated by data acquisition yet,
or a command being processed)
Operation mode
Out of service
Indicates whether the physical input/output has been decoupled by
means of property Out-Of-Service
Overridden
Object overridden by external switch
Life safety
Personal safety (Present priority is 1...3)
Locked
Locked function/object (Present priority is 4...5)
Time delay
Delay is active (Present priority is 6)
Manual switch
Switch is set to manual (Present priority is 7)
Manual Prio 8
Manual state of an object is indicated
Manual Prio 1
Alarm state
In alarm. Alarm not acknowledged.
Not in alarm. Alarm not acknowledged.
In alarm. Alarm acknowledged.
Not in alarm. Alarm acknowledged.
Not in alarm. Reset.
Primary server
Indication of primary server type (only for PX primary controllers)