Commissioning Instructions
ABT-SSA (Setup & Service Assistant)
User interface overview: Device, Field buses, Application
2
11 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Navigation pane views
The following figures outline the views for an automation station and an operating and monitoring device.
Navigation pane, automation station.
Navigation pane, operating and monitoring device.
Indicator
Name
Description
①
Device
Displays a detailed listing and state of events related to the local
device. For example, it shows whether the device is operational,
lists the available RAM and Flash memory, lists all notification
classes from 1 through 18 and provides detailed event logs
under Device > Infrastructure.
● Automation station event logging is available for all devices.
● When connected to an automation station, Alarm history and
Commissioning history event logs are also available.
②
Field buses
The Field buses view is only available when you’re connected to
a device with field buses, such as, TX-I/O, PL-Link and DALI.
Shows what devices are on the DIN rail with the automation
station.
③
Application
Displays information about the buildings and rooms being
controlled. For example, for Room 110 you can see its
application function, group master designation, supply air VAV
state, fan state, cooling coil state, and whether the room is in an
alarm state.
● Devices commissioned through the tool-free workflow display
in this view under Sites > Default.
● Devices commissioned through ABT Site display in this view
under Geographical and Functional.
For operating and monitoring devices, the Application view
provides access to modify event parameters and fault
parameters for Event Enrollment objects.